L2-CH16

On Hand Qty: 5

    190.00 190.00 190.0 USD

    190.00

    This combination does not exist.

    Add to Cart

    Zone controller module, 16 PDM Channels, dimming, communicating



    The L2-CH16 controls up to 16 zone channels of lighting from one device.  The zones are controlled via PDMbus protocol commands including scenes or zone level commands.  Each channel can command up to 64 drivers with a total limit of 128 drivers across 8 L2-DMs.  With an L2-CH16 attached to each L2-PDM, an enclosure can have up to 128 independently controlled zones via the PDMbus.  This module fits into the top channel expansion connector and communication bus connector of the L2-PDM.  It requires accessory power from an L2-APR.  Channels 9-16 must be controlled by the L2-CH16.  DIP selector switches allow channels 1-8 to be controlled either by the L2-CH16 (enable position) or by an L2-DM or L2-SW.  16 indicators LEDs show the commanded status of each channel including the dimmed level by intensity.  They are also used to indicate selected modes and configuration information. Two control buttons and status LED create a simple user interface to allow manual control of any of the channels for commissioning and configuration of the module.  The L2-CH16 appears like 16 L2-DM with a subset of configuration settings. 14 scenes may be stored across all channels. Channels may be assigned any available ID individually.

    POWER & CONNECTIONS
    Power consumed0.3 W (Requires L2-APR on the same L2-PDM)
    Top connectorMale 34 and 10 pins (Channel and PDMbus)
    Bottom connectorFemale 34 and 10 pins (Channel and PDMbus)
    ZONE CHANNEL OUTPUT
    Channel Outputs1-8optional via DIP selectors
    9-17 always controlled 
    Channel slewStaggered channel timing
    Control channel signal type0-5VDC, PWM Broadcast
    Maximum drivers controlled128
    RS485 CONTROL BUS
    Communication speed38,400 bps
    Control protocolPublished dimming module protocol
    Scenes64
    PHYSICAL/ENVIRONMENTAL
    Dimensions4.3 x 1.48 x 1.2in (110 x 36 x 30mm)
    Operating temperature+32°F to +122°F (0°C to +50°C)
    Operating humidity5% to 95% Non-condensing
    RatingDry Rated
    EnvironmentalRoHS
    Safety certificationsFCC, CE
    WARRANTY
    Duration5 Years

    PRELIMINARY
    L2-CH16 SET button and indicator LED operation:

    The green LED indicator on the lower-right, front face of the L2-CH16 indicates one of 4 Mode states (1..4) by flashing the Mode number, then a small pause, then repeating the cycle.  Wait for the pause and count the number of flashes to obtain the mode.

    Press the SET button on the face of the L2-CH16 to increment the Mode and cycle from 1 to 4 flashes (Mode 4). Pressing the SET button when you see 4 flashes will return to Mode 1 (1 flash, pause, repeat).  


    MODE

    MODE NAME

    DESCRIPTION

    1*

    Default

    Channels are controlled by the protocol commands like scenes or value change commands.

    2

    All ON

    All on set to EEPROM MAX setting PWM

    3
    Full ON
    All on set to 100% duty cycle PWM
    4All OFF
    All OFF set to 0% duty cycle PWM

    Manually set and view the ID number:

    Typically the ID #s will be assigned by the L2-EGW Gateway.  To manually assign the ID # of channel 1 of the L2-CH16, Hold the SET button for 3 seconds and release.  Then tap the SET button the number of times of the ID. The green LED will flash each time you press the SET button.  Wait 5 seconds without pressing the button and the LED will remain solid for 2 seconds indicating the ID has been stored. To check the ID, hold the SET button for 3 seconds, release, and count the LED flashes. After setting the ID of channel 1, you can reach and assign the other channel IDs via the protocol.

    PRELIMINARY

    Tool-free commissioning using Configuration Macros:

    In addition to selecting the 4 Modes of operation, the SET button can be used to run configuration macros that store advanced settings like Scenes.

    To Reset or Store values in the L2-CH16 memory, count the LED indicator flashes and set the current Mode to one of the modes in the table below, then hold the SET button for 6 seconds or until you see fast flashes for 3 seconds. This will run the Configuration Macro as follows:

    SET button RESET/STORE functions (HOLD 7 seconds to perform configuration macros)

    MODE

    DESCRIPTION

    FUNCTION(S) PERFORMED

    1

    “Factory Default”

    Resets min/max to 26/220/ch.  Mode is set to 1. Reset ID to 55-61. Erase scenes.

    2

    “-”

    -.

    3

    “-”

    -.

    4

    “-”

    -.